Graphic designations of the security alarm. Systems automatic fire extinguishing, fire, security and fire alarm

GUIDING DOCUMENT

FIRE-FIGHTING SYSTEMS,
FIRE, SECURITY AND
ALARM AND FIRE ALARM.
DESIGNATIONS CONVENTIONAL GRAPHIC
ELEMENTS OF COMMUNICATION

RD 25.953-90

I affirm

Head of Scientific and Technical
department of the Ministry of Electrotechnical Instrument of the USSR

A.I. Podaruev

APPROVAL SHEET

Automatic fire extinguishing systems, fire
security and fire alarm systems. Designations
conditional graphics systems

RD 25.953-90

General manager

NPO "Spetsavtomatika" V.D. Khazov

Head of Design

department of Standardization and Normative Control Zh.A. Zakharova

Development Manager

chief Specialist G.V. Ryzhikhina

Contractor, engineer

The alphanumeric designation of the control and start-up unit, consisting of several valves, may be written in the sequence: marks, valves, separated by a dot, diameter of the word passage and serial number, separated by a dot.

For example: KZS.BC100.1

The alphanumeric designation of the fire detector may be recorded in the sequence: number of the control panel, letter code of the detector, loop number, detector serial number. The loop number and detector serial number in the designation must be separated by a dot. Uppercase letters of the Latin alphabet are used to construct the notation.

For example: 2ВТК1.12

where 2 is the number of control panel;

VTK-letter code of the detector according to the table. of this taxiway;

1 - loop number;

12-serial detector number.

Alphanumeric designations of repeatedly repeated elements of systems are allowed to be indicated once - twice at the beginning and at the end of the image.

Name

Designation

on plans

on sections and diagrams

1. Sprinkler water sprinkler

with concave socket

with flat outlet

wall mounted

2. Water sprinkler

deluge

with concave socket

with flat outlet

Note. The designation of sprinklers with a flat outlet may be accompanied by the letter index "dp"

3. Sprinkler water deluge with a guide blade

4. Sprinkler foam sprinkler outlet

5. Sprinkler foam deluge rosette

Name

Designation

1. Automatic thermal fire detector

2. Automatic smoke detector

3. Automatic fire detector

4. Manual fire detector

5. Automatic security detector

Note: Graphic designation of detectors of optoelectronic, radio wave, ultrasound is allowed to be crossed out with the top of the triangle in the direction of the zone of its action

7. Automatic fire alarm detector

8. The annunciator is security

9. Instrument control panel

10. Unlocking device for doors, walls, ceilings, wire fences and glass to break with foil

12. Security Detector Antenna

13. Encryption

14. Reflector

15. The terminal device

16. Repeater

17. Central monitoring console

19. Transmitting camera of a television installation with a rotary device

20. Camera transmitting a television installation without a rotary device

Note. Graphic designation of elements in the sections of the table. not installed. It is allowed in accordance with the need to draw them arbitrarily, depending on the configuration of the elements.

First letter of code (required)

Element Type Group

Element Types Examples

Multi-letter code

Devices

Reception and control device, control device, central monitoring console

Perimeter alarm devices:

receiver

emitter

Camera transmitting a television installation:

with rotary device

without rotary device

Device for video monitoring of applied television installations

Executive unit of the regulator-signaling device

Converters of non-electrical quantities to electrical or vice versa analog or multi-bit.

Transducers or sensors for indicating or measuring

Automatic fire detector:

test

Manual fire detector

Automatic security detector:

electrical contact

magnetic contact

optoelectronic:

emitter

BGLI

receiver

BGLR

radio wave:

emitter

Bgoi

receiver

BGOR

piezoelectric

capacitive

inductive

contact

shock contact

magnetically operated non-contact

microphone

gas analytical

pressure

Announcer security (disturbing) manual (foot)

Automatic fire and security detector:

optoelectronic:

emitter

Bkli

receiver

Bklr

ultrasonic:

emitter

receiver

Bkfr

Fire Alarm

BIAD

sound

BIAS

light

Bial

Security announcer:

Bigd

sound

Bigs

light

Bigl

Repeater

Level sensor

Elements are different

Pyro cartridge:

directions

With a windshield

Indicating and signaling devices

Level Regulator

Pressure gauge

Switching devices in control, signaling and measuring circuits

Interim Executive Body

Button post

Limit switch on gates and doors

Locking device for doors, walls, ceilings, fences with wire and glass for breaking - with foil

Communication devices

Telephone Line Sealer

Security Detector Antenna

Contact Connections

Cable boxing

Box, drawer with clips

Distribution box

Mechanical devices with electromagnetic drive

Electric valve

Encryption device

Terminal devices with filter

Terminal device

ANNEX 1

DIMENSIONS
BASIC GRAPHIC DESIGNS

Table

Name

Designation

Water sprinkler

Foam sprinkler

Shutter head

Cable tensioning roller

Generator, involute sprinkler

Cable lock

The announcer is fire, security guard and fire

Reception and control device

Camera transmitting a television installation

Repeater

Encryption device

The annunciator is security

APPENDIX 2

Reference

SCROLL
ITEMS, CONVENTIONAL GRAPHIC DESIGNATIONS (UGO) WHICH ARE ESTABLISHED BY STANDARDS, SDDS, AND OTHER NORMATIVE-TECHNICAL DOCUMENTS

Table

Item name

The document establishing the UGO

Designation

Table number

Item Number

AUTOMATIC FIRE EXTINGUISHING SYSTEMS

Cylinder receiver

GOST 2.780

Valve (valve) shut-off

GOST 2.785

The valve (valve) regulating

GOST 2.785

Valve (valve) three-way

GOST 2.785

Hydropneumatic capacity

GOST 2.780

Pipe Connection Details

GOST 2.784

Gate valve

GOST 2.785

Automatic air valve (plunger)

GOST 2.785

Butterfly valve

GOST 2.785

Check valve (non-return valve)

GOST 2.785

safety valve

GOST 2.785

Pressure reducing valve

GOST 2.785

Compressor

GOST 2.782

End of pipe with plug (plug)

GOST 2.784

End of pipe for detachable connection

GOST 2.784

Trailer crane

GOST 2.785

Fire crane

GOST 12.1.114

Angular checkpoint crane

GOST 2.785

Three-way crane

GOST 2.785

Four way crane

GOST 2.785

Pressure gauge (general designation)

GOST 2.781

Electrical pressure gauge (pin)

GOST 2.781

Unregulated flow pump

GOST 2.782

Fire extinguisher

GOST 28130

Pipeline support

GOST 2.784

Foam mixer fire

GOST 12.1.114

Crossing of pipelines, communication lines (without connection)

GOST 2.784

Pyro cartridge

GOST 2.721

GOST 2.744

Suspension

GOST 2.784

Fluid flow

GOST 2.721

Pressure switch

GOST 2.781

Balloon reducer

GOST 2.787

Fire hose

GOST 12.1.114

2.1, 2

Connection of pipelines, communication lines

GOST 2.784

Detachable pipe connection

GOST 2.784

Manual fire barrel

GOST 12.1.114

Riser pipe

GOST 2.784

Flexible piping, hose

GOST 2.784

Pipelines, communication lines

GOST 2.784

Piping in oil seal

GOST 2.784

The pipeline in the pipe (case)

GOST 2.784

Liquid level indicator

GOST 2.781

Fire extinguishing installation

GOST 28130

Dosing devices

GOST 2.793

GOST 2.794

Throttle washer, constricting flowmeter

GOST 2.784

diaphragm

Control cabinet

GOST 21.614

ELECTRICAL CONTROL OF AUTOMATIC FIRE FIGHTING AND ALARM SYSTEMS

Rechargeable battery

GOST 21.614

Cable boxing

GOST 21.406

Switch

GOST 21.614

Automatic switch

GOST 21.614

Way switch

GOST 21.614

GOST 21.614

Level sensor

GOST 21.404

GOST 2.730

Grounding

GOST 2.721

Earthing switches

GOST 21.614

GOST 21.614

Engineering network laid in communication facilities

a) on the overpass

b) in the gallery

c) in the tunnel, the passage channel

d) in the channel through passage

d) in the cable channel

Trench engineering network

Actuating mechanism

GOST 21.404

Sewer cable

ST SEV 160

Switching device contacts

GOST 2.755

Well cable

GOST 21.406

Subscriber box

GOST 21.406

Intro box

GOST 21.614

Branch box

GOST 21.614

Lingering box

GOST 21.614

Distribution box

GOST 21.406

Box, drawer with clips

GOST 21.614

Wiring line

GOST 21.614

Pressure gauge

GOST 2.781

Cable sleeve (for communication lines)

GOST 21.406

Underground cable couplings

ST SEV 160

Fire alarm

GOST 28130

Siren Annunciator

GOST 28130

Airline Supports

ST SEV 160

Transmission line supports

GOST 21.406

Cable hole

GOST 21.406

GOST 21.614

Switch

GOST 21.614

Control switch

GOST 21.614

Pyro cartridge

GOST 2.721

GOST 2.744

Button post

GOST 21.614

Local Government Post

GOST 21.614

Alarm post central

GOST 2.758

Optical device for light signaling

GOST 2.758

Laying wires and cables

GOST 21.614

GOST 21.614

Magnetic starter

GOST 21.614

Radio outlet

GOST 21.406

GOST 21.614

Level Regulator

GOST 21.404

Variable resistor

GOST 2.728

Constant resistor

GOST 2.728

Pressure switch

GOST 2.781

Telephone socket

GOST 21.406

Socket Outlet

GOST 21.614

Lamp with incandescent lamp

GOST 21.614

Lamp with incandescent lamp for special lighting (light indicator)

GOST 21.614

GOST 21.614

Telephone stand

GOST 21.614

Scoreboard for calling personnel

GOST 21.614

GOST 28130

Power transformer

GOST 21.614

Contact device for doors, windows, floors, hatches

GOST 2.758

Starter for electric motors

GOST 21.614

Breaking device, e.g. foil strips

GOST 2.758

Electrical device General designation

GOST 21.614

GOST 21.614

Cable distribution box

GOST 21.406

Cabinets, cable

ST SEV 160

Open shield

GOST 21.614

Panel emergency lighting

GOST 21.614

One-way service shield

GOST 21.614

Airline Elements

Cylinder for a complete set of gas fire extinguishing systems BIP

Solenoid valve

Limit switch on gates and doors

Medium Foam Generator

Four-jet mesh generator

Membrane type automatic charge discharge head

Electric Shutter Head

Electric valve

Cable gate valve

Automatic security announcer

Announcer security (disturbing) manual (foot)

Automatic fire alarm

Automatic thermal fire detector

Automatic smoke detector

Automatic Flame Detector

Manual fire detector

Executive unit of the regulator-signaling device

Camera transmitting a television installation without a rotary device

Transmitting camera of a television installation with a rotary device

Air start valve

Double acting valve

7P motive valve

Rope motive valve

Electrically operated valve

Control and starting unit of an automatic fire extinguishing system

Manual fire hydrant

Firetruck with a foamy hand barrel

Gas extinguishing system nozzles

security annunciator

Drencher water sprinkler

Sprinkler water sprinkler

Sprinkler foam deluge rosette

Sprinkler foam sprinkler

Involute sprinkler

Sectional fuse

Reception and control device, control device

Rope tensioner

Interim Executive Body

Central monitoring console

Switchgear

Air distributor

Repeater

Cable tensioning roller

Reflector

Universal pressure switch

Fire monitors

Pipeline induction network gas fire extinguishing system

Compressed air line

The pipeline is vertical with the flow direction of the medium up, down

Fire extinguishing system piping

Water extinguishing system piping using a water wetter

Pipeline for gas extinguishing system

Foam fire extinguishing system piping

Locking device for doors, walls, ceilings, wire fences and glass for breaking - foil

Device for video monitoring of applied television installations

Terminal device

Launcher for gas and powder fire extinguishing systems

Telephone Line Sealer

Encryption device

I affirm
   Head of Scientific and Technical Department
   USSR Ministry of Electrical Engineering
   A.I. Podaruev 1990

APPROVAL SHEET


   The alphanumeric designation of the control-starting unit, consisting of several valves, is allowed to be written in the following sequence: marks, valves, separated by a dot, nominal diameter and serial number, separated by a dot.

For example: KZS.BC100.1

The alphanumeric designation can be written in the sequence: number, alphabetic code of the detector, number, serial number of the detector. The loop number and detector serial number in the designation must be separated by a dot. To construct the designation, capital letters of the Latin alphabet are used.

For example: 2ВТК1.12

Where 2 is the number; VTK - the alphabetic code of the detector according to Table 4 of this RD; 1 - loop number; 12 - serial number of the detector.
   Alphanumeric designations of repeatedly repeated elements of systems may be indicated once or twice at the beginning and at the end of the image.

Table 1

Name

Designation

on plans

on sections and diagrams

22. Butterfly valve

23. Head automatic discharge charge membrane type

24. Double-acting valve (for batteries type BAU, T-2ML, BAGE

25. Valve with electric start

26. Bell

27. Cylinder for a complete set of gas fire extinguishing systems BIP

28. Sectional fuse

29. Switchgear

30. Air distributor

31. Starting device for gas and


table 2

Name

Designations

3. Pipeline of a water fire extinguishing system using a water wetter

4. Pipeline gas fire extinguishing system

5. Pipeline for compressed air

6. Pipeline for gas fire extinguishing system

7. The pipeline is vertical with the flow direction of the working medium:


Table 3

Name

Designation

1. Automatic thermal fire detector

2. Automatic smoke detector

3. Automatic fire detector

4. Manual fire detector

5. Automatic security detector

Note: Graphic designation of optoelectronic detectors is allowed; cross out with a vertex of a triangle in the direction of its zone of operation

6. Announcer security (disturbing) manual (foot)

7. Automatic fire alarm detector

10. Unlocking device for doors, walls, ceilings, wire fences and glass to break with foil

11. Limit switch on gates and doors

12. Security Detector Antenna

14. Reflector

15. The terminal device

20. Camera transmitting a television installation without a rotary device

22. Interim-executive body

23. Executive unit of the regulator-signaling device


Note. The graphic designation of the elements in the sections of table 3 are not installed. It is allowed in accordance with the need to draw them arbitrarily depending on the configuration of the elements.

Table 4

First letter of code (required)

Element Type Group

Element Types Examples

Multi-letter code

Devices

Reception and control device, control device, central monitoring console


Perimeter security devices:


receiver emitter


Camera transmitting a television installation:


with rotary device
   without rotary device


Device for video monitoring of applied television installations


Executive unit of the regulator-signaling device

Converters of non-electrical quantities to electrical or vice versa analog or multi-bit. Transducers or for indicating or measuring

Automatic fire detector:

test
   smoke
   flame

VTK
   VTN
   BTF


Manual fire detector


Automatic security detector:




optoelectronic:


emitter


receiver


radio wave:
   emitter


receiver



capacitive


inductive


contact



magnetically operated non-contact


microphone


gas analytical


pressure


Announcer security (disturbing) manual (foot)


Automatic fire and security detector:


optoelectronic:


emitter


receiver



emitter


receiver


Fire Alarm




light


Security guard:



sound


light


Repeater


Level sensor

Elements are different

Pyro cartridge:


directions



With a windshield

Indicating and signaling devices

Universal pressure switch


Level Regulator


Pressure gauge

Switching devices in control circuits, and measuring

Interim Executive Body
   Button post


Limit switch on gates and doors


Locking device for doors, walls, ceilings, wire fences and glass for breaking - foil

Communication devices

Telephone Line Sealer

Security Detector Antenna

Contact Connections

Cable boxing


Box, drawer with clips


Distribution box

Mechanical devices with electromagnetic drive

Electric valve
   Encryption device

Terminal devices with filter

Terminal device

DIMENSIONS OF BASIC GRAPHIC DESIGNATIONS

   1. Recommended sizes of the main graphic symbols for the elements of automatic fire extinguishing systems, fire, security and fire alarm systems are given in the table.

Table

Name

Designation

Water sprinkler

Foam sprinkler

Shutter head

Cable tensioning roller

Generator, involute sprinkler

Cable lock

The announcer is fire, security guard and fire

Reception and control device

Camera transmitting a television installation

Medium Foam Generator

Rope tensioner

Repeater

Encryption device

The annunciator is security

ANNEX 2 Background

LIST OF ELEMENTS, CONVENTIONAL GRAPHIC DESIGNATIONS (UGO) WHICH ARE ESTABLISHED BY THE STANDARDS OF ESKD, SPDS AND OTHER REGULATORY-TECHNICAL DOCUMENTS

Table

Item name

The document establishing the UGO

Designation

Table number

Item Number

Cylinder receiver

Valve (valve) shut-off

The valve (valve) regulating

Valve (valve) three-way

Hydropneumatic capacity

Pipe Connection Details

Gate valve

Automatic air valve (plunger)

Butterfly valve

Check valve (non-return valve)

safety valve

Pressure reducing valve

Compressor

End of pipe with plug (plug)

Trailer crane

Angular checkpoint crane

Three-way crane

Four way crane

Pressure gauge (general designation)

Electrical pressure gauge (pin)

Unregulated flow pump

Pipeline support

Foam mixer fire

GOST 12.1.114

Crossing pipelines, (without connection)

Pyro cartridge

GOST 2.721 GOST 2.744

Suspension

Fluid flow

Pressure switch

Balloon reducer

Fire hose

GOST 12.1.114

Connection of pipelines, communication lines

Detachable pipe connection

Manual fire barrel

GOST 12.1.114

Riser pipe

Flexible piping, hose

Pipelines, communication lines

Piping in oil seal

The pipeline in the pipe (case)

Liquid level indicator

Fire extinguishing installation

Dosing devices

GOST 2.793
   GOST 2.794

11b)
4-6

Throttle washer, constricting flowmeter

ELECTRICAL CONTROL OF AUTOMATIC FIRE FIGHTING AND ALARM SYSTEMS

Rechargeable battery

Cable boxing

Switch

Automatic switch

Way switch

Level sensor

Earthing switches

Engineering network laid in communication facilities

a) on the overpass

b) in the gallery

c) in the tunnel, the passage channel

d) in the channel through passage

d) in the cable channel

Trench engineering network

Actuating mechanism

Sewer cable

Switching device contacts

Well cable

Subscriber box

Intro box

Branch box

Lingering box

Distribution box

Box, drawer with clips

Wiring line

Pressure gauge

Cable sleeve (for communication lines)

Underground cable couplings

Fire alarm

Siren Annunciator

Airline Supports

Transmission line supports

Cable hole

Switch

Control switch

Pyro cartridge

GOST 2.721
   GOST 2.744

Button post

Local Government Post

Optical device for light signaling

Laying wires and cables

Magnetic starter

Radio outlet

Level Regulator

Variable resistor

Constant resistor

Pressure switch

Telephone socket

Socket Outlet

Lamp with incandescent lamp

Lamp with incandescent lamp for special lighting ()

Telephone stand

Telephone Line Sealer

Encryption device

INFORMATION DATA

1. APPROVED by the Ministry of Electrical Engineering and Instrumentation of the USSR
   2. CONTRACTORS: G.V. Ryzhikhina (topic leader);
   A.M. Romanov
   3. REPLACEMENT OST 25 329 81
   4. REFERENCE DOCUMENTS
Designation of the referenced document

Number of paragraph, subparagraph, transfer, application

GOST 2.721-74

Appendix 2

GOST 2.728-74

Appendix 2

GOST 2.730-73

Appendix 2

GOST 2.744-68

Appendix 2

GOST 2.755-87

Appendix 2

GOST 2.758-81

Appendix 2

GOST 2.780-68

Appendix 2

GOST 2.781-68

Appendix 2

GOST 2.782-68

Appendix 2

GOST 2.784-70

Appendix 2

GOST 2.785-70

Appendix 2

GOST 2.787-71

Tab. 1 listing 32)

GOST 2.793-79

Appendix 2

GOST 2.794-79

Appendix 2

GOST 12.1.114-82

Appendix 2

GOST 21.108-78

Appendix 2

GOST 21.404-85

Appendix 2

GOST 21.406-85

clause 5, Appendix 2

GOST 21.614-88

clause 5, Appendix 2

GOST 28130-89

item 1, table 3 (listing 8) appendix 2

ST SEV 160-75

Appendix 2

ST SEV 5236-85

item 1

ISO 6790-86

item 1


   Material presented on the page NOT AN OFFICIAL EDITION